A fire alarm panel in trouble, a sprinkler head knocked off, a water line shut for a repair: any of these leaves a building without full protection. The Denver Fire Department (DFD) has a specific process for that situation, and missing a step can mean a Firewatch Permit you didn't plan for, or a fire watch that runs longer than it needs to.
This page walks Denver building owners and property managers through that process, based on the DFD's published System Down Reporting and Firewatch guidance (linked at the end).
Note: DFD procedures can change. Confirm current requirements with the Denver Fire Department Fire Prevention Division (720-913-3474, denfpb@denvergov.org) before you rely on this page.
Step 1: Report the system down to DFD
Any time a fire alarm or sprinkler system is compromised, Denver requires you to notify the Fire Department through its System Down Reporting website. This applies to partial impairments, not just full outages.
Step 2: Tell your monitoring company
Let your fire alarm monitoring company know the system is down. If your building has an AES (American Electronic Services) radio box, report the system offline and also call the DFD Non-Emergency Dispatch line at 720-913-2491 to tell them the system is down.
Step 3: Know the 10-hour rule (and the exception)
Fire alarm or sprinkler down for more than 10 hours: you must start a Firewatch Permit.
Any fire water line interruption, for any length of time: a Firewatch Permit is required immediately. There is no 10-hour grace period.
Once you have a Firewatch Permit, you no longer need to keep reporting daily on the System Down website.
Step 4: Get the Firewatch Permit
A Firewatch Permit can be started once a Fire Prevention Officer approves it. You then apply through Denver's E-Permits (Accela Citizen Access) system. DFD publishes a Firewatch Permit Application Guide, which is worth reading before you apply.
Step 5: Do the 30-minute walks and keep the logs
During a fire watch, someone has to walk the impacted areas every 30 minutes. Each walk is recorded on a fire watch log, which must:
stay on the premises, and
be available to Denver Fire Department personnel on request.
The Denver Fire Code also requires records of all system installations, inspections, tests, and maintenance (fire watch logs included) to be kept on site, on NFPA forms or forms provided by DFD. DFD publishes a Denver Fire Watch Log PDF you can use.
Step 6: End the fire watch
A fire watch doesn't end on its own when the system comes back. The contractor who repaired the system has to send DFD proof that the system is 100% functional:
Fire alarm: NFPA 72 System Record of Completion
Fire sprinkler or fire pump: NFPA 13 Material and Test Certificate for Fire Sprinkler Systems
That document goes by email to the Fire Prevention Division at denfpb@denvergov.org, with a short explanation of the work done and a formal request to end the fire watch.
This is where choosing the right contractor saves money: the faster the repair is done and the paperwork is filed, the sooner the fire watch (and its staffing cost) ends.
Quick checklist
Report the system down on DFD's System Down Reporting website.
Notify your monitoring company. If you have an AES box, also call 720-913-2491.
Water line interrupted? Start a Firewatch Permit now. Otherwise, start one if the system is down past 10 hours.
Get Fire Prevention Officer approval, then apply in E-Permits (Accela).
Walk impacted areas every 30 minutes and keep the logs on site.
Have your contractor email the NFPA 72 Record of Completion or NFPA 13 certificate to denfpb@denvergov.org to end the fire watch.
Frequently asked questions
How long can a fire alarm be down in Denver before a fire watch is required?
After 10 hours down, a Firewatch Permit is required. If a fire water line is interrupted, the permit is required immediately.
How often are fire watch walks required in Denver?
Every 30 minutes through the impacted areas, with each walk logged. Logs stay on the premises for DFD to review.
Who ends a fire watch in Denver?
The fire alarm or sprinkler contractor who did the repair sends DFD an NFPA 72 Record of Completion (alarm) or an NFPA 13 Material and Test Certificate (sprinkler or pump) at denfpb@denvergov.org, with a request to end the fire watch.
Do I still report daily on the System Down website during a fire watch?
No. Once a Firewatch Permit has been obtained, daily System Down reporting is no longer needed.
Need your system back online?
Life-Safety Services LLC repairs fire alarm and sprinkler systems and handles the completion paperwork DFD needs to close out a fire watch. Serving Denver and communities across Colorado. We hold Denver Fire Department license LIC00254065.
24/7 emergency service: call (720) 441-2137, or request service.
Life-Safety Services LLC, 800 E 64th Ave Unit 10, Denver, CO 80229
Source: City and County of Denver, System Down Reporting and Firewatch, checked October 19, 2026.