Denver BDA & ERRCS Requirements: A Guide for Building Owners

When firefighters go into your building, their radios have to work in every stairwell, parking level, and pump room. In Denver, that is the law, not just good practice. The 2025 Denver Fire Code is based on the 2024 International Fire Code (IFC) with local amendments. Its Section 510 sets out when a building needs emergency responder radio coverage, how a bi-directional amplifier (BDA) system has to be designed, and how often it must be tested.

This guide covers the Denver BDA requirements that owners and property managers deal with most often. All of it comes from the City and County of Denver's adopted code and Denver Fire Department (DFD) policy, linked in the Sources section at the end.

Note: Codes and DFD policies change. Always confirm current requirements with the Denver Fire Department Fire Prevention Division and a DFD-licensed ERCES contractor before you start a project.

What Is a BDA / ERRCS System?

Denver's code calls these systems ERCES (Emergency Responder Communications Enhancement Systems). DFD policy also calls them RES (Radio Enhancement Systems). In the industry they are usually called ERRCS or simply "BDA systems."

DFD Policy 510-1 describes the system as "a network of amplifiers, fiber optic cable, coaxial cable, and radiating cable and/or discrete antennas with or without a distributed antenna system (DAS) controller." It does one job: it carries the public safety radio signal from outside the building to the inside and back out.

A typical system includes:

  • A donor antenna on the roof, pointed at a public safety radio site.

  • A BDA (bi-directional amplifier), which boosts signals in both directions: downlink to the radios and uplink from them.

  • Distribution cabling and antennas (coax, fiber, or radiating "leaky" cable) running through the building.

  • A UPS and batteries that keep the system on the air during a power outage.

  • Monitoring connections to the fire alarm control panel, so failures get reported.

Denver systems operate on the city's public safety bands, 806–816 MHz and 851–861 MHz.

When Does Denver Require ERRCS?

Buildings that always need approved coverage

Under Denver Fire Code §510.1, buildings must have approved emergency responder radio coverage if they are:

  1. High-rise buildings

  2. Underground buildings

  3. Airport buildings and structures

  4. Buildings that fail the compliance testing in §510.1.1 or §510.1.2 (below)

New buildings: the coverage test

Section 510.1.1 requires new buildings to be tested at substantial construction completion if any of the following apply:

  • Type I and II buildings over 50,000 gross square feet

  • Group E and I occupancies over 12,000 gross square feet on any story

  • Type III, IV and V buildings over 100,000 gross square feet where masonry is used in shafts, walls, or above-grade floor/ceiling assemblies

  • Occupiable below-ground areas over 10,000 gross square feet

If the building lacks the required coverage, it must get an ERCES. If it passes, it must be retested every five years under DFD Policy 510-1. If DFD decides a system isn't needed, keep the written documentation of adequate coverage on site.

DFD Policy 510-1 adds an important point. Buildings that pass the initial acceptance test "will not be authorized to install a Public Safety RES system." With department approval and permits, though, the wiring and indoor antennas can be installed for future use.

Existing buildings

Under §510.1.2, testing is triggered in existing high-rise, underground, I-1, I-2, I-3, E occupancy, and airport buildings when they install a Mass Notification System (MNS) or replace the fire alarm head-end equipment entirely. If coverage is deficient, ERCES must be added. Buildings that pass are retested every five years.

What Counts as "Adequate Coverage" in Denver?

Section 510.4.1.3 of the Denver Fire Code sets these performance targets:

  • General floor area: control channel signal stronger than −100 dBm across 95% of each floor (95% service area reliability per floor and in parking areas).

  • Critical areas: 99% floor area coverage at −100 dBm or stronger in fire pump rooms, areas of refuge, fire command centers, stairways, exit passageways, main lobbies, standpipe cabinets, sprinkler sectional valve locations, and elevator lobbies.

Under the amended acceptance test procedure (§510.5.4), testing requires at least 10 sampling measurements per 16,000 square feet, or one per 40 ft × 40 ft square. Structures and parking areas are evaluated separately, and elevators, stairways, and enclosed areas are included. Where readings are marginal, DFD personnel may do a live radio test. If that fails, the grid point fails.

DFD Policy 510-1 also says a well-balanced system should ideally deliver −70 to −80 dBm throughout the building. On new installations and 5-year tests, DFD performs pass/fail audio quality testing, and the minimum passing DAQ (delivered audio quality) is 3.4.

Design and Installation Requirements

One BDA per building

Denver allows a maximum of one public safety BDA per building (§510.4.2). Buildings, towers, underground structures, and high-rises connected by common floors, parking levels, hallways, stairways, or walkways count as one building. Structures that had multiple-BDA configurations before February 1, 2018 may have to consolidate to a single BDA at the Fire Code Official's discretion.

Dedicated and standalone, built to NFPA 1225

The ERCES must be "a standalone system totally dedicated to public safety." No components can be shared with cellular or other radio systems. Design must follow Denver §510.4.2 and NFPA 1225. Any modification, repair, or removal requires approval from the fire code official.

Equipment protection and power

Section 510.4.2.10 sets these requirements:

  • Active components (BDA, DAS controller, UPS) go in a secure, conditioned, protected room separated from the rest of the building. Where NFPA 1225 requires fire-resistance-rated backbone cabling, the room must have a matching rating.

  • The UPS needs a dedicated circuit with a lock-on device. It must be connected to the emergency generator where one exists, and any cord-and-plug connection must be secured in an approved cabinet.

Battery backup

The 2024 IFC text as adopted in Denver (§510.4.2.3) requires dedicated standby batteries, or 2-hour batteries plus a connection to the facility generator. Either way, the standby supply must run the system at 100% capacity for at least 12 hours. During annual testing, DFD Policy 510-1 also checks that the UPS can power the entire system through a 4-hour test.

Donor antenna, wiring, and signage

  • The donor antenna's horizontal half-power beam width must not exceed 45 degrees. Denver advises aiming at a simulcast site at least one mile away rather than the nearest one, and the DFD Line Shop can help choose it (§510.4.2.11).

  • Amplifiers on Denver's 800 MHz network need pass-band filters that pass only 806–816 and 851–861 MHz (Policy 510-1).

  • Wiring must follow NFPA 1225 and NFPA 70. Radiating cable must be approved for use, and limited-use cable is not permitted (§510.5.7).

  • Permanent plastic or metal signs are required at the fire alarm panel and at each amplifier, stating that the building is equipped with a public safety radio repeater system (§510.5.6).

Licensed contractors only

Only contractors holding a valid Denver Fire Department license may install, modify, repair, alter, or replace an ERCES (§510.5.3).

FCC requirements

Policy 510-1 requires equipment to be FCC-certified and to comply with 47 CFR Part 90.219. Under that rule:

  • Wideband (Class B) signal boosters must be registered in the FCC signal booster database.

  • A non-licensee, such as a building owner, may operate a signal booster only with the consent of the radio system licensee.

In Denver, that licensee is the City's public safety radio system operator. Coordinate with the DFD Line Shop.

Permits and Plan Review

  • Construction permit: required to install or modify ERCES, including maintenance (§510.3.1).

  • Shop drawings: drawings that include RF grids must be submitted and approved before installation, as a deferred submittal. Handwritten notes on drawings are not accepted (§510.3.1.1).

  • Initial test first: Policy 510-1 requires the acceptance test and RF grid drawings to go to the DFD Fire Prevention Division and Line Shop before an installation is permitted. DFD decides whether a system is needed.

  • Operational permit: required for annual and 5-year testing (§510.3.2).

Permits are handled through Denver's e-permits (Accela) system.

Testing: Acceptance, Annual, and 5-Year

Acceptance testing

After installation, the contractor runs the grid test, performs the uplink noise test procedure, and sets amplifier gain with DFD Line Shop direction. DFD radio technicians then check for interference. A second set of passing RF grids is required before final inspection. New systems and 5-year tests also need an antenna isolation test, with isolation 20 dB greater than the BDA's maximum gain, plus a sweep test of donor cabling.

Annual testing (BDA testing in Denver, every year)

Under §510.6.1, the owner must have the system inspected and tested annually by a Denver ERCES-licensed contractor, and also after structural changes. Policy 510-1 says the annual test includes:

  • A visual inspection of all components

  • Verification that the BDA has no faults, amplifies the correct bands, and sends a supervisory signal to the fire alarm panel when powered down

  • The UPS 4-hour test and a check of the donor antenna mount

  • Signal verification in areas of refuge, fire command centers, stairwells, main lobbies, and elevator lobbies on the main ground floor

Documented RF grids are not required for the annual test.

5-year testing

Every five years, the system must pass the annual test items plus a full new RF grid survey and a coax sweep test. Results, new grids, and the DFD RF Survey Information Document go to DFD Fire Prevention and the Line Shop within 30 days. The 5-year test must pass an inspection witnessed by the DFD Line Shop (§510.6.1 item 5). Policy 510-1 notes that the owner pays DFD for at least two DFD radio technicians at the rate the city sets.

Records

All inspection results, uplink and downlink gain settings, maintenance records, and annual and 5-year results go in the "ERCES Maintenance and Test Results Logbook," which stays on the premises (§510.6.5).

What Happens When a System Fails?

  • Repair deadline: DFD Policy 510-1 says RES deficiencies or failed tests "shall be repaired within 72 hours." The policy is dated 2018, so confirm the current deadline with DFD.

  • Approval and retest: repairs need the appropriate permit. When the work is done, the DFD Line Shop must be notified to schedule an acceptance test.

  • Radio frequency maintenance plan: owners must keep a plan that bans electronics known to degrade coverage, allows DFD to access the site to investigate interference, and is written into every tenant's lease.

  • Firewatch: Denver's firewatch rules are written for fire alarm and sprinkler systems. For fire alarms, the Denver Fire Code requires an approved fire watch when a system is expected to be deactivated for 10 hours or more. DFD's System Down Reporting page requires reporting any compromised alarm or sprinkler system online, and a Firewatch Permit after 10 hours down, or immediately for any fire water line interruption. Fire watch patrols happen every 30 minutes and must be logged. The ERCES section does not spell out an equivalent firewatch trigger. If BDA work takes the fire alarm out of service, or if DFD requires it, assume firewatch rules apply and confirm with Fire Prevention.

Property Manager Checklist

  • Confirm whether your building is high-rise, underground, or airport, or meets a §510.1.1 size or occupancy trigger.

  • Find your most recent coverage test or written DFD "not needed" documentation, and the date the next 5-year retest is due.

  • Before an MNS installation or fire alarm head-end replacement, budget for a §510 coverage test.

  • Verify there is one public safety BDA per connected structure.

  • Check that the BDA/UPS room is secure, conditioned, and fire-rated where required.

  • Confirm the UPS circuit is dedicated, has a lock-on device, and is on the generator.

  • Verify the BDA reports a supervisory signal to the fire alarm panel.

  • Confirm the required signs are posted at the fire alarm panel and the amplifier.

  • Keep the ERCES logbook on site and up to date.

  • Confirm FCC Class B booster registration and licensee consent are on file.

  • Schedule the annual test with an operational permit, and plan the 5-year test with DFD Line Shop coordination.

  • Add the radio frequency maintenance plan language to every tenant lease.

  • Use only a contractor with a current Denver Fire Department ERCES license.

How Life-Safety Services Helps

Life-Safety Services LLC is a NICET-certified life safety contractor based at 800 E 64th Ave Unit 10, Denver, CO 80229, serving Denver and communities across Colorado. We offer BDA/ERCES design, permitting, installation, inspections, monitoring, and 24/7 emergency service, and we hold Denver Fire Department license LIC00254065.

  • Inspections and testing: annual and 5-year ERRCS testing, RF grid surveys, logbook documentation, and coordination with the DFD Line Shop.

  • Installation and upgrades: initial coverage testing for new construction, design to NFPA 1225 and Denver §510, shop drawings, and consolidation of older multi-BDA systems.

  • 24/7 emergency service: when a BDA, UPS, or fire alarm fails, help is a phone call away. 24/7 emergency service: call (720) 441-2137.

  • Monitoring: BDA supervisory and trouble signals tied into your fire alarm and monitoring service.

Frequently Asked Questions

Does every Denver building need a BDA?

No. High-rise, underground, and airport buildings require approved coverage. Other new buildings meeting the §510.1.1 size or occupancy thresholds must be tested, and they need an ERCES only if they fail the coverage test.

What signal level does Denver require?

Stronger than −100 dBm across 95% of each floor, and across 99% of critical areas such as stairways, fire pump rooms, fire command centers, and elevator lobbies (Denver Fire Code §510.4.1.3).

How often does a BDA have to be tested in Denver?

Every year, and with a full new RF grid survey every five years. Both need an operational permit, and the 5-year test must be witnessed by the DFD Line Shop.

Can our BDA share equipment with the cell phone DAS?

No. Denver requires a standalone system dedicated to public safety, with no shared components.

How long must the battery backup last?

The standby power supply must run the system at 100% capacity for at least 12 hours, using dedicated batteries or 2-hour batteries plus a generator connection.

Do we need FCC registration?

Wideband (Class B) signal boosters must be registered in the FCC signal booster database, and operation by a non-licensee requires the radio system licensee's consent (47 CFR 90.219).

Get Your Denver BDA System Tested or Installed

Whether you face a new-building coverage test, an annual or 5-year inspection, or a failed system, Life-Safety Services can help you meet Denver's ERRCS requirements. Call (720) 441-2137 or request a survey or bid.